EasyManua.ls Logo

KSB PumpDrive - Page 60

KSB PumpDrive
162 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 56: Sample parameters for closed-loop control mode using the control panel
Parameter Description Settings Factory setting
3-2-2-1
Physical unit of setpoint bar %
3-2-2-3
Physical unit of pressure bar %
3-5-1-2
Minimum setpoint 0 bar 0 %
3-5-1-3
Maximum setpoint 10 bar 100 %
3-5-4-1
Setpoint source 1 None Analog IN 1
3-5-4-2
Setpoint source 2 Configurable Setpoint Configurable Setpoint
3-5-4-3
Setpoint source 3 None Remote Setpoint
3-5-2-1
Configurable Setpoint 6,7 bar 0 %
3-8-3-1
Configuration of analog input 2 Current Current
3-8-3-2
Analog IN 2 Low current 4 mA 4 mA
3-8-3-3
Analog IN 2 High current 20 mA 20 mA
3-8-3-4
Unit of Analog IN 2 bar %
3-8-3-5
Low value for Analog IN 2 0 bar 0 %
3-8-3-6
High value for Analog IN 2 10 bar 100 %
3-9-1-6
PI Auto mode Disabled Enabled
3-9-1-1
Disable/enable PI controller Enabled Disabled
3-9-1-4
Control direction of PI controller Negative Negative
3-9-1-5
Process type of PI controller Constant pressure Constant pressure
3-9-2-1
Selection of feedback (actual
value) source
Analog IN 2 Analog IN 2
Maintain the following sequence for activating the process controller:
1.
Change parameter
3-9-1-6
.
2. Change parameter
3-9-1-1
.
The value displayed for parameter 1-3-1-3 Setpoint is 6.7 bar.
Parameter 1-3-1-1 for the actual feedback value in the corresponding unit displays
the current actual value.
7.1.1.4.2 Closed-loop control mode with external setpoint signal
By default, analog input 1 (terminal P7:9 AIN1 and 10 AGND P7) is set as the setpoint
source (
3-5-4-1
). A direct voltage of 0 to 10 V (0 to 100 %) is expected as the signal. If
a current signal, e.g. 4 - 20 mA (0 - 100 %) is to be used, the Al 1 Setting parameter
(3-8-2-1)
has to be changed accordingly. Parameters Analog IN 1 Low Voltage
(3-8-2-2)
to Analog IN 1 High Current
(3-8-2-5)
can be used to match the setpoint
input to the signal received.
PumpDrive is to control the system to achieve a setpoint of 6.7 bar in a differential
pressure control process. For this purpose, a differential pressure sensor (4 - 20 mA)
with a measuring range of 0 to 10 bar is connected to analog input 2 of PumpDrive.
The setpoint is specified using an external setpoint signal (4 - 20 mA) via analog
input 1. For the desired setpoint of 6.7 bar, 10.72 mA must be applied at analog
input 1.
Table 57: Parameters for closed-loop control mode using an external setpoint signal
Parameter Description Possible settings Factory setting
3-2-2-1
Physical unit of setpoint bar %
3-2-2-3
Physical unit of pressure bar %
3-5-1-2
Minimum setpoint 0 bar 0 %
3-5-1-3
Maximum setpoint 10 bar 100 %
3-5-4-1
Setpoint source 1 Analog IN 1 Analog IN 1
3-5-4-2
Setpoint source 2 None Configurable Setpoint
3-5-4-3
Setpoint source 3 None Remote Setpoint
3-8-2-1
Configuration of analog input 1 Current Current
3-8-2-2
Analog IN 1 Low current 4 mA 4 mA
3-8-2-3
Analog IN 1 High current 20 mA 20 mA
3-8-2-4
Unit of Analog IN 1 bar %
3-8-2-5
Low value for Analog IN 1 0 bar 0 %
3-8-2-6
High value for Analog IN 1 10 bar 100 %
3-8-3-1
Configuration of analog input 2 Current Current
Example
7 Commissioning/shutdown
60 of 162
PumpDrive

Table of Contents

Related product manuals