EasyManua.ls Logo

Laars FT Series - Boiler Component Maintenance; Air Vent Maintenance Checks; Burner Exterior Cleaning

Laars FT Series
100 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 82
- Check the air vent
If the air vent valve seems to work freely without
leaking, close cap A fully.
Loosen cap “A” one turn to allow vent to operate.
If vent does not operate correctly, replace the vent.
Maintenance procedures [Every 6 Months]
- Check the boiler piping (gas and water)
Visually inspect for leaks around internal water
piping. Also inspect external water piping,
circulators, relief valve and ttings. Immediately call
a qualied service technician to repair any leaks.
Leaks must be repaired by a qualied service
technician immediately.
Failure to comply with this instruction could result in
severe personal injury, death or substantial property
damage.
- Check the pressure relief valve
WARNING
Leaks must be xed by a qualied service technician
immediately. Failure to comply with this instruction
could result in severe personal injury, death or sub-
stantial property damage. This discharge line must
be installed by a qualied heating
installer or a service technician.
Before proceeding, verify that relief valve outlet
has been piped to a safe place of discharge within
6 to 12” from a suitable oor drain, avoiding any
possibility of scalding from hot water. If water ows
freely, release the lever and allow the valve to
seat. Watch the end of the relief valve discharge
pipe to ensure that the valve does not weep after
the line has had time to drain. If the valve weeps,
lift the seat again to attempt to clean the valve
seat. If the valve continues to weep, contact your
qualied service technician for inspecting the valve
and system. If water does not ow from the valve
even though you have lifted the lever completely, the
valve or discharge line may be blocked. Shut down
the Combination boiler immediately. Call your qualied
service technician to inspect the combination boiler
and system.
- Check the burner state
You can clean the exterior of burner with a vacuum
hose or dry cloth.. However, if you need to clean the
inside of the burner stage, you should call a qualied
service technician.
A

Table of Contents