FMS Fault Correction Correction input ( F )
Aids
F8 ___________________________________________________________________
Message The correction signal is monitored in order to be able to detect an error function
"Correction effect switched of the correction signal source (in O regulation). If a correction signal >97% is
2
off, since over 97% for present on the input for 1 hour a defect is assumed and the correction
longer than 1 hour” influence is disregarded.
__________________________________________________________________
Activate correction again
- Selector switch 1 to "Status”
- Channel 1 switch up
- Check correction effect
Selector switch (1) to "Load rating”
Press "acceptance”
- instantaneous correction input is displayed
If display >97%, check O regulator
2
_____________________________________________________________________________________________________
105