EasyManuals Logo
Home>Lamtec>Controller>FMS Series

Lamtec FMS Series User Manual

Lamtec FMS Series
162 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #118 background imageLoading...
Page #118 background image
FMS Fault Correction Parameters (P)
Aids O control
2
P33 Deactivation time for O regulation in the case of curve switching during
2
Parameter 903 operation.Switching during burner operation. The time starts from when the
Level 1 actuators have reached the "new” position.
The regulator is deactivated as soon as the switch-over starts, and the
correction value for deactivated regulation is output (parameter 902).
______________________________________________________________________________________________________
P34
Parameter 904 Delay time for activating the O regulator after the flame appears.
2
Level 1
___________________________________________________________________________________________________
P35 These parameters can be used to deactivate the O regulator below and
2
Parameters 914/915 above a defined load value. The correction value for "Deactivated O
2
Level 0 regulation” is output.
______________________________________________________________________________________________________
P36 These two parameters serve to equalise the O regulator module with an O
22
Parameters 919/920 meter coupled via an analogue signal (4...20 mA).
Level 1 Taking into account probe control during pre-ventilation, it is
recommended to set a measurement range of 0...25 vol.% O .
2
______________________________________________________________________________________________________
P37 These parameters are used to set the O monitoring bands for base and full
2
Parameters 923 to 930 load, referenced to the O2 target value in %.
Level 2 For details see page 49.
Parameters 931 to 934 Example:
Level 1 O target value 3 vol.% O
2
2
50% below threshold specified
Shut-down limit < 1.5 vol.% O .
2
______________________________________________________________________________________________________
P38 This parameter can be used to set the demand threshold for the "Dynamic
Parameter 936 probe test” function control.
Level 1 Factory setting:
2 Z 0.2 vol.% O
2
0 Z means "Dynamic probe test” switched off.
___________________________________________________________________________________________________
118

Table of Contents

Other manuals for Lamtec FMS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lamtec FMS Series and is the answer not in the manual?

Lamtec FMS Series Specifications

General IconGeneral
BrandLamtec
ModelFMS Series
CategoryController
LanguageEnglish

Related product manuals