EasyManuals Logo
Home>Lamtec>Controller>FMS Series

Lamtec FMS Series User Manual

Lamtec FMS Series
162 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #129 background imageLoading...
Page #129 background image
Appendix Notes on Start without
pre-ventilation
Minimum time for While starting without pre-ventilation there have to be 5 seconds minimum
outside light monitoring idle time betweenthe start of the system ( signal terminal 2) and the
period of the initiation of the ignition (activating the ignition transformer) to give the
flame monitoring device flame monitoring devioce enough time for "outside light monitoring".
Unless otherwise ensured, please extend parameter 755 accordingly.
________________________________________________________________
The flame monitoring device has to get minimum 5 seconds idle time for
outside light monitoring before the ignition will be initiated.
________________________________________________________________
!
129

Table of Contents

Other manuals for Lamtec FMS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lamtec FMS Series and is the answer not in the manual?

Lamtec FMS Series Specifications

General IconGeneral
BrandLamtec
ModelFMS Series
CategoryController
LanguageEnglish

Related product manuals