FMS Commissioning Tips & Tricks
Press Acceptance (3) again
- ignition position relays pull up
burner ignites
- ignition point 1 appears on display
Programming
with burner stationary Press Acceptance (3)
- ignition point 1 appears on display
72
Reversing the programming If you have started programming and do not want to save these values, but
to re-activate the old curve instead.
Selector switch (2) to "Clear memory”
Selector switch (1) to "Set-point”
Press Acceptance (3)
- “cleared” appears on the display
Selector switch (2) to Automatic
- The old curve is valid again.
___________________________________________________________________
The unit recognises that the RAM does not contain a valid curve that could
be transferred to the EEPROM. The last valid EEPROM curve is therefore
re-activated.
___________________________________________________________________
Instrumentation When commissioning systems with the FMS it is recommended that several
for commissioning 5K potentiometers with ready-made connections and at least 2 current
transmitters be always carried, (particularly where the continuous outputs
are used).
The current transmitter should be adjustable in the range 0 … 20 mA.
A voltage range of 0 … 10 V would also be advantageous in order to be able
to simulate the continuous voltage output of the FMS.
In addition 2 multimeters (measuring ranges: current, voltage, resistance)
should be to hand when commissioning.
xxx
xxx
3
2
1
xxx
LAMTECLAMTEC
xxx

Table of Contents

Other manuals for Lamtec FMS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lamtec FMS Series and is the answer not in the manual?

Lamtec FMS Series Specifications

General IconGeneral
BrandLamtec
ModelFMS Series
CategoryController
LanguageEnglish

Related product manuals