FMS Commissioning Programming Curves
_________________________________________________________
Programming the Aids
_________________________________________________________
_________________________________________________________
compound Final programming of the unit with the burner stationary can only
be done when it is certain that all feedback signals are present in
the same way as with the burner running (e.g. not
temperature-dependent or active speed feedback).
Otherwise program with burner running.
either with burner stationary
FMS
Signal on terminal 2 (burner on) = 0 Display AU
Programming can be performed only with the signal combinations
indicated. Otherwise the unit registers a fault and/or will accept no
inputs. It may be necessary to wait for the automatic firing
sequence control to release the control before programming
with the burner running (via mode "EV”, "EZ”, "EG”).
If burner drops out whilst programming in process
e.g. owing to control shut-off
- proceed to page 76 (continue programming)
If FMS skips to "ES” mode whilst programming
is in progress
- see page 76
Entirely new curve, Selector switch (1) to load rating
Clear memory - set load rating to 200 via channel 1 switch
Selector switch (1) to set-point
Mode selector switch (2) to "Clear memory”
- “SL” appears in centre of display
Press Acceptance (3):
- “cleared” appears on display
_________________________________________________________
When programming the ignition load point for the first time,
it is recommended that the FMS be initially started via the automatic
firing sequence control. At the end of the pre-ventilation time all
channels close. As soon as a switch is operated the "EI” mode is
reactivated and the ignition point can be set
_________________________________________________________
or with burner running
FMS:
Signal on terminal 2 (boiler thermostat) = 1
Wait until burner is on
_________________________________________________________
43
LAMTECLAMTEC
xxx
xxx
xxx
xxx
3
2
1
SETPOINT
ENTER
CLEAR
MEMORY
LOAD RATING
(CORR. INPUT)

Table of Contents

Other manuals for Lamtec FMS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lamtec FMS Series and is the answer not in the manual?

Lamtec FMS Series Specifications

General IconGeneral
BrandLamtec
ModelFMS Series
CategoryController
LanguageEnglish

Related product manuals