Settings List of Parameters
(Level 0 and 1 parameters only)
Para- Short Safety Lower Upper
meter- design- level limit limit Standard
No. nation Description values Aids
_____________________________________________________________________________________________________
1 P30
897 O2Stoer 1 0 2 O
2
0 P31
898 O2-TotZ 0 3 20 15 P32
899 O2-P-Fak 0 1 50 O P-factor 5 P32
2
900 O2 TZ - 0 0 5 O
2
3 P32
901 O2Neutr1 1 0 1000 Correction value output on deactivated
O regulation. Fuel 1 300 P31
2
902 O2Neutr2 1 0 1000 Correction value output on deactivated
O regulation. Fuel 2 300 P31
2
903 O2FWZeit 1 0 9999 O deactivated after fuel
2
change in sec.. 30 P33
904 O2WarteZ 1 0 9999 O regulation active after
2
ignition in sec. 90 P34
910 O2Totbnd 2 0 10 O lag band in 0.1% 2
2
914 O2Aktiv 0 0 999 Activate O regulation from
2
load position X (in pts) 0 P35
915 O2Deakti 0 0 999 Deactivate O regulation from
2
load position X (in pts) 999 P35
917 LftmKor1 1 0 999 Air shortage correction value, fuel 1 150 P31
918 LftmKor2 1 0 999 Air shortage correction value, fuel 2 150 P31
919 O2 4mA 1 0 999 O value 4mA 0 P36
2
920 O2 20mA 1 0 999 O value 20mA 250 P36
2
931 O22UBU1G 1 0 250
100 P37
932 O22UBU1V 1 0 250
100 P37
933 O22UBU2G 1 0 250
100 P37
934 O22UBU2V 1 0 250
100 P37
936 O2SOWert 0 0 65535 2 P38
Parameter for O regulation
2
896 O2Regler 0 0 9 O -Regulator
2
0 = O regulator off 8 = Only display, base value
2
1 = Standard regulator for deact. O regulator
2
2 = Without lag time 9 = Only display, base value
3 = only display for air shortage
neutral value
Error shut-down by regulator
permitted (0=No, 1=on air shortage)
Lag time of the O regulation section
2
Lag time shortening of the regulation
section with full load
Lower 2nd monitoring band, fuel 1
in % of target value, base load
Lower 2nd monitoring band, fuel 1
in % of target value, full load
Lower 2nd monitoring band, fuel 2
in % of target value, base load
Lower 2nd monitoring band, fuel 2
in % of target value, full load
Probe dynamic test
29

Table of Contents

Other manuals for Lamtec FMS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lamtec FMS Series and is the answer not in the manual?

Lamtec FMS Series Specifications

General IconGeneral
BrandLamtec
ModelFMS Series
CategoryController
LanguageEnglish

Related product manuals