Settings List of Parameters
(Level 0 and 1 parameters only)
Para- Short Safety Lower Upper
meter- design- level limit limit Standard
No. nation Description values Aids
_____________________________________________________________________________________________________
689 Unt.Mo5 1 0 999 Monitor output, curve set 5: 0 P10
4 mA correspond to X points
690 Unt.Mo6 1 0 999 Monitor output, curve set 6: 0 P10
4 mA correspond to X points
691 Unt.Mo7 1 0 999 Monitor output, curve set 7: 0 P10
4 mA correspond to X points
692 Unt.Mo8 1 0 999 Monitor output, curve set 8: 0 P10
4 mA correspond to X points
693 Ob.Mo1 1 0 999 Monitor output, curve set 1: 999. P10
20 mA correspond to X points
694 Ob.Mo2 1 0 999 Monitor output, curve set 2: 999 P10
20 mA correspond to X points
695 Ob.Mo3 1 0 999 Monitor output, curve set 3: 999 P10
20 mA correspond to X points
696 Ob.Mo4 1 0 999 Monitor output, curve set 4: 999 P10
20 mA correspond to X points
697 Ob.Mo5 1 0 999 Monitor output, curve set 5: 999 P10
20 mA correspond to X points
698 Ob.Mo6 1 0 999 Monitor output, curve set 6: 999 P10
20 mA correspond to X points
699 Ob.Mo7 1 0 999 Monitor output, curve set 7: 999 P10
20 mA correspond to X points
700 Ob.Mo8 1 0 999 Monitor output, curve set 8: 999 P10
20 mA correspond to X points
Flying curve change
702 Luftvor 1 0 999 Air advance with flying 0 P11
curve change in points
703 Dauer LV 1 0 999 Duration of air advance with flying 0 P11
curve change in seconds
704 Wirku LV 1 0 999 Effect on air advance 1 P11
0-Load / 1-Setting
Band shift
707 Wirk.Bve 1 0 1 Effect on band shift 0 P2
0-Load / 1-Setting
708 BandV K1 1 0 50 Band shift 4 P3
Channel 1
709 BandV K2 1 0 50 Band shift 4 P3
Channel 2
710 BandV K3 1 0 50 Band shift 4 P3
Channel 3
23