System Operation Messages / Faults
Fault code number Aids
st
H / Ü 191* 1 monitoring band exceeded for too long: channel 1 B1,B3
st
H / Ü 192* 1 monitoring band exceeded for too long: channel 2 B1,B3
st
H / Ü 193* 1 monitoring band exceeded for too long: channel 3 B1,B3
st
H / Ü 194* 1 monitoring band exceeded for too long: channel 4 B1,B3
st
H / Ü 195* 1 monitoring band exceeded for too long: channel 5 B1,B3
st
H / Ü 201* 1 monitoring band not attained for too long: channel 1 B1,B3
st
H / Ü 202* 1 monitoring band not attained for too long: channel 2 B1,B3
st
H / Ü 203* 1 monitoring band not attained for too long: channel 3 B1,B3
st
H / Ü 204* 1 monitoring band not attained for too long: channel 4 B1,B3
st
H / Ü 205* 1 monitoring band not attained for too long: channel 5 B1,B3
H / Ü 211 2nd monitoring band exceeded for too long: channel 1 E11,B5
H / Ü 212 2nd monitoring band exceeded for too long: channel 2 E11,B5
H / Ü 213 2nd monitoring band exceeded for too long: channel 3 E11,B5
H / Ü 214 2nd monitoring band exceeded for too long: channel 4 E11,B5
H / Ü 215 2nd monitoring band exceeded for too long: channel 5 E11,B5
H / Ü 221 2nd monitoring band not attained for too long: channel 1 E11,B5
H / Ü 222 2nd monitoring band not attained for too long: channel 2 E11,B5
H / Ü 223 2nd monitoring band not attained for too long: channel 3 E11,B5
H / Ü 224 2nd monitoring band not attained for too long: channel 4 E11,B5
H / Ü 225 2nd monitoring band not attained for too long: channel 5 E11,B5
H 231** Compound sticking: channel 1 E2,E4,E5
C1,B1,B3
H 232** Compound sticking: channel 2 E2,E4,E5
C1,B1,B3
H 233** Compound sticking: channel 3 E2,E4,E5
C1,B1,B3
H 234** Compound sticking: channel 4 E2,E4,E5
C1,B1,B3
H 235** Compound sticking: channel 5 E2,E4,E5
C1,B1,B3
H / Ü 301* Wire break on correction input, channel 1 F2
H / Ü 302* Wire break on correction input, channel 2 F2
H / Ü 320* Wire break load input D7
85

Table of Contents

Other manuals for Lamtec FMS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lamtec FMS Series and is the answer not in the manual?

Lamtec FMS Series Specifications

General IconGeneral
BrandLamtec
ModelFMS Series
CategoryController
LanguageEnglish

Related product manuals