6 Correcting Faults
6.1.2 Warnings
Warning no. Warning text
001 (HP)
101 (ÜP)
O
2
offset voltage in the air too large or too small
/1 - 29999 Trigger value of the O
2
offset voltage in the air (x0.1 mV)
002 (HP)
102 (ÜP)
CO offset voltage in the air too large or too small
/1 - 29999 Trigger value of the CO offset voltage in the air (x0.1mV)
003 (HP)
103 (ÜP)
O
2
temperature too large or too small, was not assumed
invalid calibration (p. ex. with calibration gas >14,9 vol % O
2
). The new O
2
temperature is not accepted. The O
2
measurement remains/will be
improper.
/1 - 29999 Trigger value of the O
2
temperature (x0.1 K)
004 (HP)
104 ÜP
CO temperature too large or too small, was not assumed
invalid calibration (p. ex. with calibration gas >14,9 vol % O
2
). The new
CO temperature is not accepted. The CO
e
value remains/will be improper.
/1 - 29999 Trigger value of the CO temperature (x0.1 K)
Help:
When calibrating the O
2
electrode in CO containing flue gas the O
2
sen-
sors’ Kelvin value moves outside the permissible range
(< 800 ... >1200 K). The warning WH004 or WH104 is indicated CO
temperature is too high/too low.
The calibration have to be repeated on another point of O
2
without CO in
the flue gas.
005 (HP)
105 (ÜP)
CO scaling
/1 CO value not assumed, CO setpoint value too small
/2 CO value not assumed, division by zero
/3 CO value not assumed, calibration scaling factor outside of the valid
range
Help:
CO sensor worn/poisoned. Exchange the probe.
/4 CO value not assumed, value is zero
010 (HP)
110 (ÜP)
For LT3-F: Internal resistance of ceramics of the O
2
electrode
over 45 Ω
For LT3: Internal resistance of ceramics of the O
2
electrode
over 80 Ω
/0 - 65535 Trigger value of current internal resistance (x0.1 ),
tolerance time of 3 seconds.
011 (HP)
111(ÜP)
For LT3-F: Internal resistance of ceramics of the CO electrode
over 45 Ω
For LT3: Internal resistance of ceramics of the CO electrode
over 80 Ω
/0 - 65535 Trigger value of current internal resistance (x0.1 ,
tolerance time of 3 seconds.
016 (HP)
116 (ÜP)
Internal warning

Table of Contents

Other manuals for Lamtec LT3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lamtec LT3 and is the answer not in the manual?

Lamtec LT3 Specifications

General IconGeneral
BrandLamtec
ModelLT3
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals