8 Options
8.1.2 Factory Setting of Analogue Outputs via LSB Module
The module is activated at the factory.
In case of a later installation or exchange, the LSB address 19 must be set on the module us-
ing only 2 rotary switches.
Analogue output 1 (O
2
measured value)
Setting range adjustable between 0 ... 25 % O
2
Factory setting: 0 ... 10 vol.% O
2
4 ... 20 mA
Analogue output 2 (CO
e
measured value)
Setting range adjustable between 0 ... 30,000 ppm
Factory setting: 0 ... 1,000 ppm 4 ... 20 mA
Analogue outputs 3 and 4 are currently deactivated at the factory and/or reserved for other
values, such as flue gas temperature and efficiency.
1 Analogue output module Terminal assignment:
2 LSB terminal resistance, 120 1+ / 1- Analogue output 1
3 Rotary switch for setting the tens
LSB address
2+ / 2- Analogue output 2
4 Rotary switch for setting the ones
LSB address
3+ / 3- Analogue output 3
5 Jumper plug 4+ / 4- Analogue output 4
24 VDC Voltage supply for LT3 Terminals
77-/78+
CAN H/L LAMTEC SYSTEM BUS for LT3
Terminals 74 H/75 L

Table of Contents

Other manuals for Lamtec LT3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lamtec LT3 and is the answer not in the manual?

Lamtec LT3 Specifications

General IconGeneral
BrandLamtec
ModelLT3
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals