8 Options
8.4 Technical Data for HART Module
Setting of LSB address not necessary.
8.4.1 Functional Description
Current module: 2 analogue outputs 0/4 ... 20 mA
HART communication (SLAVE) via analogue output 1
NOTICE
All outgoing lines from the HART module must be screened. The screens must be applied to
the PE rail as short as possible.
NOTICE
The termination resistor (120 ) must be installed and activated on the first and the last BUS
device.
Avoid transmission line!
Terminal assignment:
1+ / 1- Analogue output 1 and HART communication (SLAVE)
2+ / 2- Analogue output 2
24 VDC Voltage supply for LT3 Terminals 77-/78+
CAN H/L LAMTEC SYSTEM BUS for LT3 Terminals 74 H/75 L