61
8 Options
8.2.2 Factory Setting of the Digital Outputs
The LSB module for digital outputs 1 ... 4 is activated at the factory. In case of a later installa-
tion or exchange, the LSB address 03 must be set on the module using only 2 rotary switches.
The LSB module for digital outputs 5 ... 8 is activated at the factory. In case of a later installa-
tion or exchange, the LSB address 51 must be set on the module using only 2 rotary switches.
Digital output 1
Term. 13/14
Locked faults
Digital output 2
Term. 23/24
Warning
Digital output 3
Term. 33/34
Limit value 1 (exceeding of 400 ppm CO
e
, 60 s)
Digital output 4
Term. 43/44
Limit value 2 (undershooting of 0.5 vol. % O
2
, 30 s)
Digital output 5
Term. 13/14
Calibration
Digital output 6
Term. 23/24
Cold start
Digital output 7
Term. 33/34
Measure
Digital output 8
Term. 43/44
Warning

Table of Contents