8.5.5 External Connection
NOTICE
It is prohibited to use the terminals!
Recommendation for line lengths and line cross-sections of the LAMTEC SYSTEM
BUS:
0 - 40 m 2 x 2 x 0.34 mm
2
, cabled in pairs with screening, impedance 120
40 - 300 m 2 x 2 x 0.5 mm
2
, cabled in pairs with screening, impedance 120
300 - 500 m 2 x 2 x 0.75 mm
2
, cabled in pairs with screening, impedance 120
Example cable type for fixed installation:
LAPP cable 2170267 (LAMTEC article no.: 05L05 2 x 2 x 0.5).
HELU cable 800685.
8.6 LSB Module for Calculating Combustion Efficiency
Setting of LSB address not necessary.
Terminals may not be connected!
1 CAN/LSB
2 DC power supply
(safety extra low voltage)
Terminals may not be connected!