(f) EMG: “EMERGENCY” . Red
Active (on) when the equipment is in a state of emergency operation (voice alarm) or by
manual or automatic activation from the CIE, of any of the voice alarm zones. When the
system is in a state of emergency and it is broadcasting a spoken voice, either through the
emergency microphone or by a prerecorded evacuation message, the indicator light will flash.
(g) FLT/DIS: “FAULT / DISARMED” . Amber
Active (on) when the voice evacuation channel is turned off.
Active (flashing) when a fault is detected on a voice evacuation channel. This indicator
is activated automatically upon detection of failure of any supervised functions in the channel.
If none of the indicators of general supervised function is on, it will indicate a fault in the
speaker's line. Restart the fault condition.
(h) SIGNAL: “SIGNAL”. Green
Active (on) when it detects an amplifier channel output signal from the corresponding
voice evacuation zone. The minimum level at which the indicator lights is -50dB.
2.1.3 SUPERVISED FUNCTION INDICATORS
Supervised Functions indicators show the faults that affect the general system
functions.
i) CIE: “CIE” / “ECI”
Active (on) when a failure occurs in the transmission line between the CIE and the
system. Reset fault condition. If fault the persists, see chapter 5.2 for its resolution. Amber
colour.
j) PROTECT: “PROTECTION”
Active (on) when any of the system protection devices are active. Restart the fault
condition. Reset fault condition. If the fault persists, see chapter 5.3 for its resolution. Amber
colour.
k) POWER: “POWER” / “ALIMENTACIÓN”
Active (on) when there is a power failure in the system. It may be due to a failure at the
main power supply or at the emergency power supply. Reset fault condition. If the fault
persists, see chapter 5.4 for its resolution. Amber colour.
l) LINK: “LINK” / “ENLACE”
Active (on) when there is a link failure between the equipment, and some elements of
the distributed system. Reset fault condition. If the fault persists, see chapter 5.5 for its
resolution. Amber colour.
m) SYSTEM: “SYSTEM” / “SISTEMA”
Active (on) when there is a failure in the execution of the equipment's software, or in its
memory. Reset fault condition. If the fault persists, see chapter 5.6 for its resolution. Amber
colour.
2.1.4 EMERGENCY SOURCES INCDICATORS
Emergency sources indicators indicate the operating status of prerecorded messages,
and the emergency microphone.
(n) EVAC: “EVACUATION”
Active (on) when the evacuation message is being broadcast in the selected voice
alarm zone. Red colour.
(o) ALERT: “ALERT”
Active (on) when the alert message is being broadcasted in the selected voice alarm
zone. Amber colour.
LDA Audio Tech - Severo Ochoa Nº 31- 29590 MÁLAGA, ESPAÑA. Tlf: +34 952028805