Table 2. Limits for particulates and gases
Contaminant Limits
Gaseous Severity level G1 as per ANSI/ISA 71.04-1985
1
, which states that the reactivity rate of copper
coupons shall be less than 300 Angstroms per month (Å/month, 0.0039 μg/cm
2
-hour weight
gain).
2
In addition, the reactivity rate of silver coupons shall be less than 200Å/month (≈ 0.0035
μg/cm
2
-hour weight gain).
3
The reactive monitoring of gaseous corrosivity must be conducted
approximately 5 cm (2 in.) in front of the rack on the air inlet side at one-quarter and three-quarter
frame height off the floor or where the air velocity is much higher.
Particulate Data centers must meet the cleanliness level of ISO 14644-1 class 8. For data centers without
airside economizer, the ISO 14644-1 class 8 cleanliness might be met by choosing one of the
following filtration methods:
The room air might be continuously filtered with MERV 8 filters.
Air entering a data center might be filtered with MERV 11 or preferably MERV 13 filters.
For data centers with airside economizers, the choice of filters to achieve ISO class 8 cleanliness
depends on the specific conditions present at that data center.
The deliquescent relative humidity of the particulate contamination should be more than 60%
RH.
4
Data centers must be free of zinc whiskers.
5
1
ANSI/ISA-71.04-1985. Environmental conditions for process measurement and control systems: Airborne
contaminants. Instrument Society of America, Research Triangle Park, North Carolina, U.S.A.
2
The derivation of the equivalence between the rate of copper corrosion growth in the thickness of the corrosion
product in Å/month and the rate of weight gain assumes that Cu2S and Cu2O grow in equal proportions.
3
The derivation of the equivalence between the rate of silver corrosion growth in the thickness of the corrosion
product in Å/month and the rate of weight gain assumes that Ag2S is the only corrosion product.
4
The deliquescent relative humidity of particulate contamination is the relative humidity at which the dust absorbs
enough water to become wet and promote ionic conduction.
5
Surface debris is randomly collected from 10 areas of the data center on a 1.5 cm diameter disk of sticky
electrically conductive tape on a metal stub. If examination of the sticky tape in a scanning electron microscope
reveals no zinc whiskers, the data center is considered free of zinc whiskers.