Step 8. If you are installing a NVIDIA FHHL V100 GPU, do the following:
1. One V100 GPU air baffle supports up to two FHHL V100 GPUs installed. If you are installing
two FHHL V100 GPUs, remove the middle plate from the V100 GPU air baffle. If you are
installing one FHHL V100 GPU, go to the next step.
Figure 97. Middle plate removal
2. Install the V100 GPU air baffle.
Figure 98. V100 GPU air baffle installation
After installing a GPU with the GPU thermal kit, continue to install other PCIe adapter if necessary. See
“Install a PCIe adapter on the riser assembly” on page 168.
Install a PCIe adapter
Use this information to install a PCIe adapter on the riser assembly or on the system board.
This topic contains the following information:
“Install a PCIe adapter on the riser assembly” on page 168
“Install a PCIe adapter on the system board” on page 173
Install a PCIe adapter on the riser assembly
Use the following information to install a PCIe adapter on the riser assembly.
Read the
installation
Guidelines” on
page 126
Power off
the server for
this task” on
page 194
ATTENTION:
Static Sensitive Device
Ground package before opening”
on page 127
168 ThinkSystem SR650 Setup Guide