5
Electrical installation
Connection of relay output K
SR
for Safe standstill"
EDK82EV113 DE/EN/FR 8.1
L
108
K32
33
34
X3.1
K31
8200 vector
X3.1
34
+
33
K32 K31
+5V
DC
+24V
=
K
SR
IGBT
8200vec266
Fig. 1 Relay K
SR
Terminal assignment Data
33 Reference potential for the input
safety shutdown
Safety relay
Coil voltage at +40°C DC +24 V (+19.5 ... 36 V)
Coil current at 24 V DC 30 mA
Test voltage contact coil AC 1500 V
eff
for 1 min
34 Input safety shutdown
Test voltage contact contact AC 1500 V
eff
for 1 min
Electrical endurance at rated load ~ 10
7
switching operations
Mechanical endurance ~ 10
7
switching operations
K31
Feedback contact
Feedback contact
Switching voltage DC 24 V
K32 Continuous current 5 ... 700 mA