Commissioning
Selection of the correct operating mode
EDK82EV113 DE/EN/FR 8.1
L
116
Application Operating mode
Stand−alone drives
Setting in C0014
recommended alternatively
with extremely alternating loads 4 2
with heavy start conditions 4 2
with speed control (speed feedback) 2 4
with high dynamic response (e. g. positioning and infeed drives) 2 −
with torque setpoint 5 −
with torque limitation (power control) 2 4
Three−phase AC reluctance motors 2 −
Three−phase sliding rotor motors 2 −
Three−phase motors with fixed frequency−voltage characteristic 2 −
Pump and fan drives with square−law load characteristic 3 2 or 4
Group drives
(several motors connected to controller)
identical motors and identical loads 2 −
different motors and/or changing loads 2 −
C0014 = 2: linear V/f characteristic control
C0014 = 3: square−law V/F characteristic control
C0014 = 4: Vector control
C0014 = 5: sensorless torque control