Commissioning
Using the keypad E82ZBC − Parameter setting
7
EDK82EV113 DE/EN/FR 8.1
121
L
The menu user − The 10 most important drive parameters
After mains switching or plugging in the keypad during operation, the 10 codes defined in
code C0517 are immediately available.
In default setting the menu user contains all codes required for a standard application with
linear V/f characteristic control.
Code Name Lenze setting
C0050 Output frequency Display: Output frequency without slip compensation
C0034 Setpoint selection range 0
Standard I/O X3/8: 0 ... 5 V / 0 ... 10 V / 0 ... 20 mA
Application I/O
X3/1U: 0 ... 5 V / 0 ... 10 V
X3/2U: 0 ... 5 V / 0 ... 10 V
C0007 Fixed configuration of digital inputs 0
E4 E3 E2 E1
CW/CCW DCB JOG2/3 JOG1/3
CW/CCW rotation DC injection
brake
Selection of fixed setpoints
C0010 Minimum output frequency 0.00 Hz
C0011 Maximum output frequency 50.00 Hz
C0012 Acceleration time main setpoint 5.00 sec
C0013 Deceleration time main setpoint 5.00 sec
C0015 V/f rated frequency 50.00 Hz
C0016 V
min
boost Depending on the controller
C0002 Parameter set management Restore default setting; Transfer parameter sets with keypad; save, load
or copy own basic settings
) Note!
Use C0002 "Parameter set transfer/restorage of default setting" to transfer
configurations from one controller to the other with keypad or restore the
default setting by loading the Lenze setting (e.g. if you lost track during
parameter setting).