7
Commissioning
Using the keypad E82ZBC − Linear V/f characteristic control
EDK82EV113 DE/EN/FR 8.1
L
124
Switch−on sequence Note
10. Set the acceleration time T
ir
(C0012)
Lenze setting: 5.00 s
[ H z ]
2
C 0 0 1 1
1
0
t
i r
t
i f
T
i r
T
i f
t
T
ir
+t
ir
@
C0011
f
* f
t
ir
= acceleration time wanted
11. Set the deceleration time T
if
(C0013)
Lenze setting: 5.00 s
T
if
+t
if
@
C0011
f
* f
t
if
= deceleration time wanted
12. Set the V/f−rated frequency (C0015)
Lenze setting: 50.00 Hz
100%
0
0 C0015
U
min
U
out
f
13. Set the V
min
boost (C0016)
Lenze settings: Depending on the controller type
The Lenze setting is suitable for all
common applications
14. If you want to change the settings, please go to
the menu
ALL .
activate e. g. JOG frequencies
(C0037, C0038, C0039) or motor
temperature monitoring (C0119)
When you are ready with parameter setting:
15. Setpoint selection e. g. via potentiometer at the
terminals 7, 8, 9
16. Enable the controller.
20
28
X3
misc002
Terminal X3/28 = HIGH
17. The drive should be running now at e.g. 30 Hz
000
0050
000
1
abcde
j
gfkih PS
mno
p
qr
Hi
Hz
Lo
3
If the drive does not start, press
in addition.