EasyManua.ls Logo

Lenze 8400 - Page 55

Lenze 8400
94 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EDS84AYCER EN 2.0 - 11/2010 L 55
E84AYCER communication manual (PROFINET)
Parameter data transfer
Reading parameters from the controller
Parameter response after a correct read request
Parameter response to a read error
Byte 1 Byte 2 Byte 3 Byte 4
Request reference Response identifier Axis Number of indices
0xXX 0x01 0x00 0x01
(mirrored) Parameter read (mirrored)
Byte 5 Byte 6
Format Number of values
0x43 0x01
Double word 1 value
Byte 7 Byte 8 Byte 9 Byte 10
Value
High word: high byte High word: low byte Low word: high byte Low word: low byte
0x00 0x00 0x00 0x2B
Read value = 0x00 00 00 2B = 43 x 1 (internal factor) = 43 [°C]
Byte 1 Byte 2 Byte 3 Byte 4
Request reference Response identifier Axis Number of indices
0xXX 0x81 0x00 0x01
(mirrored) Parameter not read (mirrored)
Byte 5 Byte 6
Format Number of values
0x44 0x01
Error Error code without additional
information
Byte 7 Byte 8
Error code
High byte Low byte
For meaning see chapter "Error information (error)"