Lenze · E94AYCET communication module (EtherCAT®) · Communication Manual · DMS 10.2 EN · 11/2018 · TD06 43
6 Commissioning
6.6 Establishing an online connection with the »Engineer«
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
How to configure an online connection to a field device which is connected to the Lenze
Controller via EtherCAT:
1. Go to the "Communication path" dialog box and select the entry "Gateway controller ->
EtherCAT" from the "Bus connection" list field.
2. Click Search/Enter....
The "Gateway Controller -> Set up EtherCAT bus" dialog box is shown:
3. Enter the IP address of the controller.
By clicking the Ping button, you can carry out a simple test which verifies whether a device
can actually be reached via the IP address set.
4. Click OK.
The "Enter IP address" dialog box is closed.
•In the Device access path column of the "Communication path" dialog box, the
corresponding device access path is shown
(e.g. "IPC:172_31_207_254.ECAT.ecat1.dev1001.").