9 Parameter data transfer
9.4 SDO abort codes (Abort codes)
80
Lenze · E94AYCET communication module (EtherCAT®) · Communication Manual · DMS 10.2 EN · 11/2018 · TD06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.4 SDO abort codes (Abort codes)
If an SDO request is evaluated negatively, a corresponding error code is output.
Index [hex] Description
0x00000000 No error
0x05030000 The status of the toggle bit has not changed
0x05040000 SDO protocol time-out
0x05040001 Invalid or unknown specification symbol for the client/server command
0x05040005 The space in the main memory is not sufficient.
0x06010000 Access to object not supported
0x06010001 Read access to a write-only object
0x06010002 Write access to a read-only object
0x06010004 Complete Access (is not supported)
0x06020000 An object does not exist in the object directory
0x06040041 An object cannot be entered/mapped in the PDO.
0x06040042 The number and/or length of the objects entered/mapped would exceed the PDO length.
0x06040043 General parameter incompatibility
0x06040047 General internal device incompatibility
0x06060000 Access has failed due to a fault in the hardware
0x06070010 The data type or the parameter length does not correspond
0x06070012 Incorrect data type (The parameter length is too large)
0x06070013 Incorrect data type (The parameter length is too small)
0x06090011 A subindex is not available
0x06090030 The value range for parameters is too great (only for write access)
0x06090031 The parameter value is too high
0x06090032 The parameter value is too low
0x06090036 The maximum value is lower than the minimum value
0x08000000 General error
0x08000020 Data cannot be transferred to the application or stored in the application
0x08000021 Due to local control, data cannot be transferred to the application or stored in the
application
0x08000022 Due to the current device state, data cannot be transferred to the application or stored in the
application
0x08000023 The dynamic generation of an object directory has failed, or no object directory is available.