7 Data transfer
7.3 EtherCAT state machine
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
7.3 EtherCAT state machine
Before communication is possible via EtherCAT, the fieldbus passes through the EtherCAT state
machine during start-up. The following illustration depicts the possible state changes from the
point of view of an EtherCAT slave:
[7-1] EtherCAT state machine
The current status of the EtherCAT state machine is shown in C13861 / C14861 and is indicated via
the RUN LED.
E94AYCET009
Operational
Pre-Operational
Init
Safe-Operational
Status Description
Init Initialisation phase
No SDO/PDO communication with the slaves
Device can be detected by fieldbus scan
Pre-Operational The fieldbus is active.
SDO communication (mailbox communication) is possible.
No PDO communication
Safe-operational SDO communication (mailbox communication) is possible.
PDO communication:
The input data in the process image are updated.
The output data from the process image are not transferred to the slaves.
Operational Normal operation:
SDO communication
PDO communication
Fieldbus synchronisation has been successful (if used)
Note!
A fieldbus scan can be carried out during any EtherCAT status.
SDO communication via the EtherCAT bus is only possible if at least the "Pre-
Operational" state has been reached.