9 Parameter data transfer
9.2 Reading and writing parameters
76
Lenze · E94AYCET communication module (EtherCAT®) · Communication Manual · DMS 10.2 EN · 11/2018 · TD06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
SDO Download Response
Detailed breakdown of the data for an "SDO Download Response":
SDO frame area Data field Data type / length Value / description
Mailbox header Length WORD 2 bytes 0x0A: Length of the mailbox service data
Address WORD 2 bytes Station address of the source if an EtherCAT
master is the initiator.
Station address of the target if an EtherCAT slave
is the initiator.
Channel WORD 6 bits
(0 ... 5)
0x00: Reserved
Priority 2 bits
(6, 7)
0x00: Lowest priority
...
0x03: Highest priority
Type 4 bits
(8 ... 11)
0x03: CANopen over EtherCAT (CoE)
Reserved 4 bits
(12 ... 15)
0x00
CANopen header Number WORD 9 bits
(0 ... 8)
0x00
Reserved 3 bits
(9 ... 11)
0x00
Service 4 bits
(12 ... 15)
0x03: SDO response
SDO Size indicator BYTE 1 bit
(0)
0x0
Transfer type 1 bit
(1)
0x0
Data set size 2 bits
(2, 3)
0x0
Complete access 1 bit
(4)
0x00: The entry addressed with index and
subindex is written.
0x01: The complete object is written. (Currently
not supported.)
Command specifier 3 bits
(5 ... 7)
0x3: Download response
Index WORD 2 bytes Index of the object
Subindex BYTE 1 byte Subindex of the object
0x00 or 0x01 if "Complete access" = 0x01.
Reserved DWORD 4 bytes 0x00