Appendix
Code table
14−23
L
EDB82MV752 EN 5.2
Code IMPORTANTPossible settings
No. SelectionLenzeName
C0141* Setpoint
normalisation
0.00 −100.00 {0.01 %} 100.00 The value set will be lost when
switching the mains!
Only effective if C0127 = 1
Reference: C0011
C0142
Start condition 1
0 Automatic restart after mains connection
inhibited
Flying restart not active
Start after HIGH−LOW−HIGH changes at
X3/28
7−18
1 Automatic start, if X3/28 = HIGH
Flying restart circuit not active
2 Automatic restart after mains connection
inhibited
Flying−restart circuit active
Start after HIGH−LOW−HIGH changes at
X3/28
3 Automatic start, if X3/28 = HIGH
Flying restart circuit active
C0143*
Selection of
flying−restart
0
0 Max. output frequency (C0011) ... 0 Hz
Motor speed selected for the indicated
range
7−18
1 Last output frequency ... 0 Hz
2 Frequency setpoint addition (NSET1−NOUT)
The corresponding value is input after
controller enable.
3 Act. process controller value (C0412/5) addition
(PCTRL1−ACT)
C0144
No temperature
depending
switching frequency
derating
1 0 No temperature−depending switching frequency
derating
When operating with a switching frequency
of 16 kHz it is also possible to derate it to 4
kHz. The behaviour can be changed under
C0310.
7−14
1 Automatic switching frequency derating to 4 kHz,
if
max
reaches
− 5 °C
C0145*
Process controller
setpoint source
0
0 Total setpoint (PCTRL1−SET3) Main setpoint + additional setpoint
7−53
1 C0181 (PCTRL1−SET2)
Setpoint selection not possible via
JOG values
function of the keypad
C0044, C0046 and C0049
in connection with manual/remote
changeover, skip frequencies, ramp
function generator, additional setpoint
Activate the automatic DC−injection
brake (auto DCB) with C0019 = 0 or
C0106 = 0
2 C0412/4 (PCTRL1−SET1)
C0148*
Motor parameter
identification
0
0 Ready
Only when the motor is cold!
1. Inhibit controller, wait until drive is at
standstill
2. Enter the correct motor data under
C0087, C0088, C0089, C0090, C0091
(see motor nameplate).
3. Set C0148 = 1 by
4. Enable controller
The identification
starts, goes off
the motor makes a high−pitched tone,
but does not rotate!
takes approx. 30 s
is completed when
is on again
5. Inhibit controller
7−48
1 Start identification
V/f−rated frequency (C0015), slip
compensation (C0021) and motor stator
inductivity (C0092) are calculated and saved.
The motor stator resistance (C0084) = total
resistance of motor cable and motor is
measured and saved