Fusing data
Inverter i550-C5.5/230-3
Cable installaon in compliance
with
EN 60204-1
without mains choke
Circuit breaker
Characteriscs B
Max. rated current A 32
Fuse
Characteriscs gG/gL or gRL
Max. rated current A 32
with mains choke
Circuit breaker
Characteriscs B
Max. rated current A 32
Fuse
Characteriscs gG/gL or gRL
Max. rated current A 32
Earth-leakage circuit breaker
3-phase mains connecon ≥ 300 mA, type B
Technical data
3-phase mains connecon 230/240 V
Fusing data
104