Fusing data
Inverter i550-C1.1/230-2 i550-C1.5/230-2 i550-C2.2/230-2 i550-C4.0/230-3
Cable installaon in compliance
with
US Naonal Electrical Code NFPA 70 / Canadian Electrical Code C22.1
without mains choke
Circuit breaker
Characteriscs -
Max. rated current A 30 30 30 -
Type of fusing Standard -
SCCR: requirement Standard short-circuit strength -
SCCR: max. short circuit cur-
rent
kA 5 5 5 -
SCCR: voltage 240 Volts Maximum -
Fuse
Characteriscs all acc. to UL 248 / Class CC all acc. to UL 248 /
Class J, T, R
Max. rated current A 30 30 30 40
Type of fusing Standard
SCCR: requirement Standard short-circuit strength
SCCR: max. short circuit cur-
rent
kA 5 5 5 5
SCCR: voltage 240 Volts Maximum
with mains choke
Circuit breaker
Characteriscs -
Max. rated current A 30 30 30 -
Type of fusing Standard -
SCCR: requirement Standard short-circuit strength -
SCCR: max. short circuit cur-
rent
kA 5 5 5 -
SCCR: voltage 240 Volts Maximum -
Fuse
Characteriscs all acc. to UL 248 / Class CC all acc. to UL 248 /
Class J, T, R
Max. rated current A 30 30 30 40
Type of fusing Standard
SCCR: requirement Standard short-circuit strength
SCCR: max. short circuit cur-
rent
kA 5 5 5 5
SCCR: voltage 240 Volts Maximum
Earth-leakage circuit breaker
3-phase mains connecon ≥ 30 mA, type B ≥ 300 mA, type B
Technical data
3-phase mains connecon 230/240 V
Fusing data
106