Inverter i550-C5.5/400-3 i550-C7.5/400-3 i550-C11/400-3 i550-C15/400-3
Rated power kW P
N
5.5 7.5 11 15
Rated power hp P
N
7.5 10 15 20
Mains voltage range 3/PE AC 340 V ... 528 V, 45 Hz ... 65 Hz
Output voltage 3 AC 0-400/480 V
Rated mains current
without mains choke A I
r, AC
17.2 20 28.4 38.7
with mains choke A I
r, AC
12.4 15.7 22.3 28.8
Apparent output power kVA A
ON
8.7 11 16 22
Rated output current
2 kHz A I
OUT
13 16.5 23.5 32
4 kHz A I
OUT
13 16.5 23.5 32
8 kHz A I
OUT
13 16.5 23.5 32
16 kHz A I
OUT
8.7 11 15.7 21.3
Power loss
2 kHz W 137 172 242 340
4 kHz W 145 185 260 360
8 kHz W 190 240 340 460
16 kHz W 189 238 337 469
at inverter disablecontroller
inhibit
W 6 6 6 18
Overcurrent cycle 180 s
Max. output current A I
max, out
19.5 25 35 48
Overload me s t
ol
60 60 60 60
Recovery me s t
re
120 120 120 120
Max. output current during the
recovery me
A 9.8 12.4 17.6 24
Overcurrent cycle 15 s
Max. output current A I
max, out
26 33 47 64
Overload me s t
ol
3 3 3 3
Recovery me s t
re
12 12 12 12
Max. output current during the
recovery me
A 9.8 12.4 17.6 24
Cyclic mains switching 3 mes per minute
Brake chopper
Max. output current A I
max, 1
16.6 29 29 43
Min. brake resistance Ω R
min
47 27 27 18
Max. motor cable length shielded
without EMC category m 100 100 100 100
Category C1 (2 kHz, 4 kHz, 8
kHz)
m - - - -
Category C2 (2 kHz, 4 kHz, 8
kHz)
m 20 20 20 20
Category C3 (2 kHz, 4 kHz, 8
kHz)
m 35 50 50 35
Weight kg 2.3 3.7 3.7 10.3
Weight lb 5 8 8 23
Technical data
3-phase mains connecon 400 V
Rated data
114