Inverter i550-C110/400-3
Rated power kW P
N
110
Rated power hp P
N
150
Mains voltage range 3/PE AC 340 V ... 528 V, 45 Hz ... 65 Hz
Output voltage 3 AC 0-400/480 V
Rated mains current
without mains choke A I
r, AC
-
with mains choke A I
r, AC
168
Apparent output power kVA A
ON
142
Rated output current
2 kHz A I
OUT
180
4 kHz A I
OUT
180
8 kHz A I
OUT
162
16 kHz A I
OUT
108
Power loss
2 kHz W 2163
4 kHz W 2305
8 kHz W 2717
16 kHz W 2717
at inverter disablecontroller
inhibit
W 30
Overcurrent cycle 180 s
Max. output current A I
max, out
270
Overload me s t
ol
60
Recovery me s t
re
120
Max. output current during the
recovery me
A 135
Overcurrent cycle 15 s
Max. output current A I
max, out
360
Overload me s t
ol
3
Recovery me s t
re
12
Max. output current during the
recovery me
A 135
Cyclic mains switching 1 me per minute
Brake chopper
Max. output current A I
max, 1
333
Min. brake resistance Ω R
min
2.4
Max. motor cable length shielded
without EMC category m 100
Category C1 (2 kHz, 4 kHz, 8
kHz)
m -
Category C2 (2 kHz, 4 kHz, 8
kHz)
m 20
Category C3 (2 kHz, 4 kHz, 8
kHz)
m 100
Weight kg 35.6
Weight lb 78.5
Technical data
3-phase mains connecon 480 V
Rated data
162