User Manual 10H52188UM51 - Rev. 1 - 09/2011 11
Liebert NXC Product Introduction
Item
Specifications
LI6010… (10kVA) LI6015... (15kVA) LI6020… (20kVA)
EMC
Conduction emission IEC/EN 62040-2
Immunity I
16A, IEC/EN 61000-3-3; 16A < I
75A, IEC/EN 61000-3-11
Harmonic current I
16A, IEC/EN 61000-3-2; 16A < I
75A, IEC/EN 61000-3-12
Surge protection
IEC/EN 61000-4-5, endurance level 4 (4kV) (live line to earth),
level 3 (2kV) (during live lines)
Protection level IP20
Ambient
condition
Operating temperature 0°C ~ 40°C
Storage temperature
-40°C ~ +70°C (battery excluded); -20°C ~ +55°C (battery
included)
Relative humidity 5%RH ~ 95%RH, non-condensing
Altitude
< 2000m; derating according to GB/T3859.2 when higher than
2000m
Size W × H × D 500mm × 1240mm × 860mm
Weight
Net weight
215kg with Battery 32 Blocks
315kg with Battery 64 Blocks
415kg with Battery 96 Blocks
520kg with Battery 128 Blocks
115kg without Battery
Gross weight
245kg with Battery 32 Blocks
345kg with Battery 64 Blocks
445kg with Battery 96 Blocks
550kg with Battery 128 Blocks
145kg without Battery

Table of Contents