Stove Installation (for qualified installers only) 11
© Travis Industries 100-01282_000 4111128
Chimney Requirements
DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.
DO NOT CONNECT TO OR USE IN CONJUNCTION WITH ANY AIR DISTRIBUTION DUCTWORK
UNLESS SPECIFICALLY APPROVED FOR SUCH INSTALLATIONS
IN CANADA: This appliance must be connected to a factory-built chimney conforming to CAN/ULC-
S629, Standard for 650°C Factory-Built Chimneys.
UL 103 HT Chimney must be used from the first ceiling or floor or wall penetration to the chimney
cap.
Use 6" (152mm) diameter type UL 103 HT chimney from one manufacturer (do not mix brands) or
code approved masonry chimney with a flue liner.
Chimney must be fastened to each adjoining section.
Follow the chimney manufacturer's clearances and requirements.
Use the chimney manufacturer's fire stops, attic guards, roof supports, and flashings when passing
through a ceiling and roof (see “b” and “d” below).
No more than 180
o
of elbows (two 90
o
elbows, or two 45
o
& one 90
o
elbow, etc.) may be used for the
entire system (connector and chimney).
NOTE: Additional elbows may be allowed if draft is sufficient. Whenever elbows are used the draft is
adversely affected. Additional chimney height may be required to boost draft.
(a) Min. System Height 15’ (4.5M)
Max. System Height 33’ (10.058M)
(b) Roof Penetration and Termination (see
chimney manufacturer’s requirements)
(c) Chimney Sections
(d) Ceiling Penetration (see chimney
manufacturer’s requirements)
(e) Minimum air space to combustibles (see
chimney manufacturer’s requirements –
typically 2” / 51mm)
(f) Connector – see “Chimney Connector” on
the previous page.
Figure 4
Drafting
Performance
This appliance relies upon natural draft to operate. External forces, such as wind,
barometric pressure, topography, or factors of the home (negative pressure from exhaust
fans, chimneys, air infiltration, etc.), may adversely affect draft. Travis Industries cannot be
responsible for external forces leading to less than optimal performance.








}
}

}