Press the [◀] key to move to the 10s place position.
Press the [▲] or [▼] key to change the ‘0’ to ‘9’ of the target
code, ’93.’
Press the [ENT] key.
Code H 93 will be displayed.
Press the [ENT] key once again.
The current parameter value for code H93 is set to 0 (Do not
initialize).
Press the [▲] key to change the value to 1 (All Grp), and then press
the [ENT] key.
The parameter value will flash.
Press the [ENT] key once again.
Parameter initialization begins. Parameter initialization is complete
when code H93 reappears on the display.
Following parameter initialization, all parameters are reset to factory default values. Ensure that
parameters are reconfigured before running the inverter again after an initialization.
1.3.3 Read and Write Parameters
Read and Write Setting Details
Copies saved parameters from the inverter to the keypad. Saved parameters on
the keypad will be deleted and replaced with copied parameters.
Take caution when Parameter write (H92) is executed. By doing this, parameters
in inverter are cleared and parameters in remote keypad are copied to inverter.
* Available on LCD keypad only.