3. Maintenance
3.1.4 Checking the Input/Output Modules
How to check the diode module and IGBT module (SV004~075iG5A-2/4)
Testing method
1) Disconnect all power cables (R,S,T) and motor output cables (U,V,W)
2) Before testing, check the discharge of electrolytic capacitor (DCP-DCN)
3) When the circuit is open, the DMM indicates a high resistance (several MΩ). In some situations the DMM may
indicate a closed circuit (low resistance) and then indicate a high resistance due to the capacitors. When the
circuit is closed, the DMM indicates a resistance of several hundred or less.
4) Displayed values may not be constant as they depend on the module and tester type. However, the value
measured between phases can be considered satisfactory if the measured value is within ±10%
Module
Test Polarity
Check Value
Module
Test Polarity
Check Value
+
-
+
-
Diode
D1
R
DCP+
Closed
D4
R
DCN
Open
DCP+
R
Open
DCN
R
Closed
D2
S
DCP+
Closed
D5
S
DCN
Open
DCP+
S
Open
DCN
S
Closed
D3
T
DCP+
Closed
D6
T
DCN
Open
DCP+
T
Open
DCN
T
Closed
IGBT
Tr1
U
DCP
Closed
Tr4
U
DCN
Open
DCP
U
pen
DCN
U
Closed
Tr2
V
DCP
Closed
Tr6
V
DCN
Open
DCP
V
Open
DCN
V
Closed
Tr3
W
DCP
Closed
Tr2
W
DCN
Open
DCP
W
Open
DCN
W
Closed