External fault
A contact
input
Normal open contact input. When a P7 terminal set to “Ext
trip-A” is ON (Closed), inverter displays the fault and turns
off its output.
External fault
B contact
input
Normal close contact input. When a P8 terminal set to “Ext
trip-B” is OFF (Open), inverter displays the fault and turns
off its output.
The terminal set to “18 (External
fault-A)” or “19 (External fault-B)”
in I20-I24 in I/O group is ON.
Eliminate the cause of fault at circuit connected to external fault
terminal or cause of external fault input.
When inverter operation is set via Analog input (0-10V or
0-20mA input) or option (RS485) and no signal is applied,
operation is done according to the method set in I62
(Operating method when the frequency reference is lost).
No frequency command is
applied to V1 and I.
Check the wiring of V1 and I and frequency reference level.
Remote
keypad
communicatio
n error
Displayed when inverter and remote keypad does not
communicate each other. It does not stop Inverter
operation.
Communication error between
inverter keypad and remote
keypad.
Check for connection of communication line and connector.