2. Troubleshooting
25
LCD Display
Type
Description
Low
Voltage
Trip
Level
Displayed when internal DC circuit voltage is less than the
specified value.
Cause
Remedy
The input voltage is too low.
Determine if the input voltage is below the specified value.
The actual DC link voltage is
different from the displayed
value..
Need to inspect hardware. Contact the retailer or the LSIS customer
service center.
Blackout accidents occur
Use speed search function
An input phase-loss has
occurred.
Check the input wiring.
The magnetic contactor
connected to the power source
has a faulty connection.
Replace the magnetic contactor.
A load greater than the power
capacity is connected to the
system (e.g., a welder, direct
motor connection, etc.)
Increase the power capacity.
LCD Display
Type
Description
Electronic
Thermal
Latch
Displayed based on inverse time-limit thermal
characteristics to prevent motor overheating.
Cause
Remedy
The motor has overheated.
Reduce the load or operation frequency.
The inverter load is greater than
the rated capacity.
Replace the inverter with a model that has increased capacity.
The set value for electronic
thermal protection(ETH) is too
low.
Set an appropriate electronic thermal level(ETH).
The inverter has been operated
at low speed for an extended
duration.
Replace the motor with a model that supplies extra power to the
cooling fan.