2. Troubleshooting
20
Category
LCD Display
Details
Page
Brake control error
P. 27
Level type
Operating method when the
frequency command is lost
P. 26
Low voltage fault trip
P. 25
Instant cut off
-
Fatal type
Hardware fault
P. 27
Warning
Over Load
Over load warning
-
* Overload Protection
IOLT : IOLT(inverter Overload Trip) protection is activated at 150% of the inverter rated current for 1
minute and greater.
OLT : OLT is selected when F56 is set to 1 and activated at 200% of F57[Motor rated current] for 60 sec
in F58. This can be programmable.
iG5A is not provided with “Over speed Protection.”