Displayed when the DC circuit in the inverter detects a
specified level of excessive, short circuit current..
Acc/Dec time is too short,
compared to load inertia (GD2).
Output wiring is short-circuited.
There is a inverter-motor
connection problem.
Check the output wiring
Ensure that the total cable length between the inverter and the motor
is less than 200m (50m for motors rated 3.7 kW or lower).
There is a fault with the output
module (IGBT).
Refer to 3.1.4 Checking the Input/Output Modules on page38 and
check a fault with the output module(IGBT)
Do not operate the inverter. Contact the retailer or the LSIS customer
service center.
The inverter turns off its output when a ground fault occurs
and the ground fault current is more than the internal
setting value of the inverter.
A ground fault has occurred in
the inverter output wiring.
There is a inverter-motor
connection problem.
Check the output wiring
Ensure that the total cable length between the inverter and the motor
is less than 200m (50m for motors rated 3.7 kW or lower).
The motor insulation is
damaged.
Noise occurs in the peripherals
Change the carrier frequency to the minimum value in H39