Displayed when a 3-phase inverter output has one or more
phases in an open circuit condition.
The magnetic contactor on the
output side has a connection
fault.
Check the magnetic contactor on the output side.
The output wiring is faulty.
Displayed when a fault condition occurs in the inverter
cooling fan..
A foreign object is obstructing
the fan’s air vent.
Remove the foreign object from the air inlet or outlet.
The cooling fan needs to be
replaced.
Replace the cooling fan. (Refer to 3.1.3 Replacement of the cooling
fan)
The inverter turns off its output if the DC voltage of the main
circuit increases higher than 400 V when the motor
decelerates. This fault can also occur due to a surge
voltage generated at the power supply system.
The input voltage is too high.
Determine if the input voltage is above the specified value.
The actual DC link voltage is
different from the displayed
value..
Need to inspect hardware. Contact the retailer or the LSIS customer
service center.
Deceleration time is too short for
the load inertia (GD2).
Increase the acceleration time.
A generative load occurs at the
inverter output.