Loading...
Under Indicator
* The data save into the SD card will show
" 9999 " or " 999 " (overleap the decimal point ).
Data Hold Freeze the display reading.
Data Record SD Card Record.
Sampling Time Approx. 1 second.
Power ON/OFF Manual OFF by push button.
Real time * Real time data logger, saved the data
data logger into SD memory card and down load
the all the measured value with the
time information ( year/month/date/
hour/minute/second ) down load
to the Excel.
* Sampling time for data logger :
2 seconds to 7200 seconds, the during
of setting step are 2 seconds.
* Data error no. :
0.1% no. of total saved data typically.
Data Output RS232 computer serial interface :
USB/RS232 * Connect the optional USB cable
* Computer USB-01 will get the USB plug.
interface * Connect the optional RS232 cable
UPCB-02 will get the RS232
plug.
Operating 0 to 50 ( 32 to 122 ).
Temperature
Operating Less than 80% R.H..
Humidity
Power Supply * DC 1.5V, AA ( UM-3 ) Battery X 8 PCs
(Alkaline or heavy-duty battery).
* AC to DC 9V power adapter.
Power * Meter : 362 DCmA.
Consumption * Clamp : 22 DCmA.
Clamp max. 50 mm ( 2.0 inch ) Dia.
conductor Size * For the Clamp ,CP-1201
4