38 Programming Guide
Connecting Fire Circuits and PGMs
N.C. Contacts, with EOL Resistor, with Tamper and Wire Fault
Recognition (UL/cUL)
Parallel Wiring
Program the PGM with the
[ ] Key was pressed”
Activation Event so that
the smoke detectors can
be reset by pressing the
[
CLEAR] + [ENTER] keys for
three seconds. See Event
Group # 6 on page 14.
All 4-wire smoke
detectors must be
connected using the
daisy chain
configuration
Each MG5000 control
panel supports a
maximum of five
2-wire smoke
detectors