CHALLENGERSERIES10‐60KVA PRODUCTDESCRIPTION
AG–SD‐35Rev.No:1Rev.Date:25.09.2013PublicationNo:2 19
2.3.2AdvancedLevelFunctions(AutomaticBatteryTest)
Theautobatterytestdischarges30%ofthebatteryenergyinauserdefinedperiod(defaultis
90days).Thisperiodcanbeadjustedbetween30‐360days.Testreportsthebatterycondition
as“goodorreplace”.Resultsofthelatesttestcanbeseenonthebatteryscreenfromthe
statusmenu.
WARNING:Ifthetestresultisreplace”,thenthebatteriesarecompletelydrainedduringthe
test.Thissituationmaycausetheloadremainedunpoweredincaseofmainsvoltageisoutof
thelimitsormainspoweroff.
Thistestcanbestartedbycommandfromfrontpanelmonitor,via TELNET interface, via
RS232smartcommunicationorviaMAKNET(SNMP,seetheoptions).
Itischeckedthatifthebatteriescansupplytheminimumbackuptimeneededincaseofthe
firstpoweroffbyusingtheresultsofallthesetests.Checkingthetestresultswitharegular
periodisrecommended.