2.3.2AdvancedLevelFunctions(AutomaticBatteryTest)
Theautobatterytestdischarges30%ofthebatteryenergyinauserdefinedperiod(defaultis
90days).Thisperiodcanbeadjustedbetween30‐360days.Testreportsthebatterycondition
as“goodorreplace”.Resultsofthelatesttestcanbeseenonthebatteryscreenfromthe
statusmenu.
WARNING:Ifthetestresultis“replace”,thenthebatteriesarecompletelydrainedduringthe
test.Thissituationmaycausetheloadremainedunpoweredincaseofmainsvoltageisoutof
thelimitsormainspoweroff.
Thistestcanbestartedbycommandfromfrontpanelmonitor,via TELNET interface, via
RS232smartcommunicationorviaMAKNET(SNMP,seetheoptions).
Itischeckedthatifthebatteriescansupplytheminimumback‐uptimeneededincaseofthe
firstpower‐offbyusingtheresultsofallthesetests.Checkingthetestresultswitharegular
periodisrecommended.