CHALLENGERSERIES10‐60KVA INSTALLATION
AG–SD‐35Rev.No:1Rev.Date:25.09.2013PublicationNo:2 31
3.1.2.2InternalBatteryConfiguration
10‐30kVAUPScanbeconfiguredby28‐50pcs7Ahor9AhbatteriesaccordingtoUPS’s
powerstandardasfollowing.
Challenger2InternalBatteryUsageTable
UPSPower(KVA)
10 15 20 30
SerialBattery
Number
28 38 40 28 38 40 38 40 38 40
BatteryGroup
1 2 1 2 1 2 1 2 1 2 1 1 2 1 2 2 2
TotalNumberof
Batteries
28 56 38 76 40 80 28 56 38 76 40 38 76 40 80 76 80
I_bat_max@
V_bat_cutoff.(A)
29,6 21,8 20,7 44,4 32,7 31,1 43,6 41,4 65,4 62,1
Recommended
InternalFuse(A
40 50 50 80
Recommended
Back‐CoverFuse(A)
40 50 50 2X40
*Thesetableshowstherecommendedbatteryconfigurations.
*Fastandsemi‐conductorprotectiontypeoffuseisusedforbatteries.
Thefollowinggeneralbatterysafetyprecautionsandwarningsshouldbeobservedatall
times:
Donotdisposeofbatteryinfire
Donotattemptopenthebatteries.
Eyeprotectionshouldbeworntopreventinjuryfromelectricalarcs.
Removerings,watches,necklaces,braceletsandallothermetalobjects.
Useonlytoolswithinsulatedhandles.
Wearrubberglovesandarubberapronwhenhandlingbatteries.
Ifabatteryleakselectrolyteorisotherwisedamaged,itshouldbeplacedinacontainer
resistanttosulfuricacidanddisposedofinaccordancewithlocalregulations.
Ifelectrolytecomesintocontactwiththeskintheaffectedareashouldbewashedimmediately
withplentyofcleanwater.
Ensurecorrectconnectionsofparalelandseriescables.