CHALLENGERSERIES10‐60KVA INSTALLATION
AG–SD‐35Rev.No:1Rev.Date:25.09.2013PublicationNo:2 30
3.1.2Positioning
Keepthedeviceinacoolanddryplacepriortoinstallation.
NOTE:Unusedbatteriesmustbechargedperiodically.
3.1.2.1PositioningTheUPS
TheUPSandthebatteriesaredesignedforindooruse,andmustbeplacedonanareawith
coolairflow.
Airentersthedevicefromthefrontsideventilationholes,goesoutfromthefansontherear
sideofthedevice.Caremustbetakeninordernottocovertheairenteranceandexitspots.
Iftheareaisdusty,Optionalfiltersmustbeusedondustyenvironments.
During operation, there is a remarkable amount of heat loss to room air, so an air
conditioningsystemmustbeusedtokeepthetemperatureinlimits.
UPS
AmountofBTU/hfor
cooling
B
ridgeLoad100%(Nonlineer)estimated
BTU/hvalueforload
working
10 KVA 3100 3700
15 KVA 4100 5000
20 KVA 5500 6600
30 KVA 7800 9400
40 KVA 9900 11900
60 KVA 14800 17800