CHALLENGERSERIES10‐60KVA SAFETYANDWARNINGS
AG–SD‐35Rev.No:1Rev.Date:25.09.2013PublicationNo:2 9
1.2ClearanceandAccess
Clearance
There is no any air inlet or outlet grill on the left or right sides of our 10-60 kVA UPS. All air
goes in to UPS from the front and is evacuated from the rear through fans. There must be spaces
at least 1 meter for UPS's front side and 1,2 meter at the back side. Should not be permanent or
temporary use within the limits specified. Otherwise, the UPS performance will decrease.
Access
Operator reaches UPS via front panel on 10-60 kVA UPS. Therefore, enough area must be left for
operator. Also, UPS can be intervened in the back of it for service and maintenance. Because of
this reason , enough area for personal must be left at the rear side of UPS. There is no limit to the
sides of the device.
1.3Storage
UPS should be kept in a room or area where is protected from excessive moisture and heat before
commissioning..
WARNING:
Unused batteries must be charged at regular intervals. This time interval is determined by the
battery supplier. Charging can be performed periodically by connecting to a proper mains for a
while.
1.4Shipment
CarryingvehiclesmusthaveenoughfeaturesandcharacteristicstocarryUPS.
Cabinetisequippedwithfour‐wheel.Inthisway,itcanbeplacedbymovingeasily.These
wheelsareusedonlysmoothsurfaces.
TherearwheelsofUPSmustbelockedafterpositioningproperly.Therearsidewheelsare
fixed.
Bemorecarefulofsuddenmovements,especiallywhenbatteriesareinsideofcabinet.
MovetheUPSasrarelyaspossible.