EasyManua.ls Logo

MAKELSAN Challenger Series - 6 Technical Specifications

MAKELSAN Challenger Series
72 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.TechnicalSpecifications
TechnicalSpecifications
Power
10kVA 15kVA 20kVA 30kVA 40kVA 60kVA
Active Power
8kW 12kW 16kW 24kW 32kW 48kW
Input
InputVoltageRange 220±%15(L‐N)or380±%15(L‐L)3P+N+PE
InputPowerFactor AtFullLoad>0,99
InputFrequencyRange 50Hz±10%/60Hz±10%(Adjustable)
Rectifier IGBTRectifier
TotalHarmonicDistortion
(THDi)
<%5
Output
OutputVoltageRange
220/380VAC(230/400VACadjustable)3P+N±1%Static,±1%
Dynamic
Recovery
At0%‐ 100%‐ 0%load,maximumoutputtolerance%5,%1Backto
band<40ms
Efficiency Upto%93
OutputFrequencyRange
synchronouswiththenetworkattherangeof50Hz±2%,mains
whenisoutofrange50Hz
±0,2%,batterymode50Hz±0,2%
OutputTHD(THDv)
Lineer<%3
Non‐Lineer<%4
CrestFactor(CF) 3:1
OverloadCapacity At%125load10min.,at%150load1min.
Protections
Theinputvoltageisoutoftolerance,inputfrequencyisoutoftolerance,
i
nputphasefailure,outputvoltageisoutoftolerance,outputfrequencyis
o
utoftolerance,outputphasefailure,DCcomponentthatcanoccuratthe
outputvoltage,Overloadthatwilloccurattheoutput(outoftheperiods
specified),Overheatingthatwillcausefailurerelatedtoover
t
emperature,highvoltagewhichwilloccuratDCBusvoltage,lowvoltage
whichwilloccuratDCBusvoltage,shortcircuitattheoutput.
Battery
Quantity(12VDCVRLA)
28‐50 38‐50 48‐50 50
ChargeValue(C)
Nominal0.1C,adjustable.
BatteryPower
25%ofthedevicepower