LEVELUPS SERIES 10-20 KVA PRODUCT DESCRIPTION
AG-SD-83 / Publication Date: 15.09.2014 / Rev. No: 0 / Rev. Date:
2.4.4 Password-protected menus
Some menus such as the control menu are
password protected. Press to set each digit and
press ENTER to confirm.
2.4.5 Control Menu
Within the control menu, you can do one of the following:
Start Start the UPS
Stop Stop the UPS
Switch to BYPASS Switch to static BYPASS mode
Switch to UPS Switch to online mode
Bat. Quick Test Start the quick battery test
Bat. Capacity Test Start the deep battery test
Stop Battery Test Stop the battery test
Battery status test, drains the 10% of battery
energy and reports batteries
which has more capacity than 10% as “Good”, less
capacity than 10% as “Replace” according to the test
results.
After UPS is started, it makes quick battery test every
24 hours and when test counter value is zero (0).
Note: Batteries must be fully charged and kept floating for at least 1 hour before applying the
quick battery tests.
Batteries must be fully charged and kept in floating mode for at least 5 hours before performing
the battery tests.