LEVELUPS SERİSİ 10-20 KVA OPERATION
AG-SD-83 / Publication Date: 15.09.2014 / Rev. No: 0 / Rev. Date:
4.1.4 Performing a Complete Shutdown
1. Turn off the loads connected to the device.
2. Use the front panel to turn the device OFF
Main Menu> Control> Password> Stop
3. Check if the the UPS has switched to bypass mode, via mimic diagram LEDs and LCD panel.
4. Turn OFF respectively the output(CB3), battery (CB4), outer battery (CB5) and input (CB1) .
WARNING :
Make sure that there are no critical loads on the UPS output before
performing a complete shutdown.